Fuse Protection

We often check out older systems which were installed by the owner and often find that the fuse protection is inadequate. This can be quite a dangerous situation and for the record, 'solar powered' houses have burned down due to inadequate protection.

Unless you are electrically trained, we really feel that installations should be carried out by trained personnel. This is quite a complex issue, so the following article is not meant to be a detailed or complete instruction on how to do it. You should also be aware that standards may vary in different countries.

If you have any doubts about your system, we strongly suggest you have it checked by a qualified person.

The main reason for adequate fuse protection is to prevent over heating of the cables in a fault or overload situation which, if unprotected, could result in a fine. In some cases (particularly motors and pumps) the manufacturer may recommend a fuse to help prevent damage to the motor if it starts to draw excessive current.

How often have you heard on the news that a house burned down due to 'an electrical fault!?' This is usually caused by inadequate fusing on cables where the 2 live conductors come into contact with each other. The insulation being eaten by animals is the most common cause of failure (rodents, termites, birds etc). The other common cause of failure is mechanical damage often caused by wind or motor vibration or by people pulling on a wire instead of the plug itself. Even a 12 volt battery system is quite capable of causing a fire in a fault situation.

The key principle of fusing is that each wire in a circuit must be protected by a breaker or fuse. This fuse must be rated less than the ampacity or current carrying capacity (ccc) of the cable.

Fuse ratings for the wire sizes that we sell are:

Cable Size (mm²)Rating (amps)
1.84 15
2.9 20
4.6 25
7.9 45
13.6 70
32 110
49 150

You can use a smaller fuse but not a larger one!

If you have 2 wire sizes on the one circuit you either need 2 appropriately sized fuses, unless the fuse for the smaller cable will handle the load carried by the larger cable. A common example of this in a 12/24 volt household is when you use a small gadget that comes with a cigarette type plug on the end. Always make certain there is a fuse inside the cigarette lighter plug as this type of power lead is often rather flimsy and prone to mechanical damage.

In general terms, you can use any appropriately rated fuse or circuit breaker in your battery type system. However, for the large cables that connect onto the battery, you should use a sealed type of fuse (usually HRC type) and not a circuit breaker which could generate sparks if it tripped. Sparks near the explosive gases generated by a charging battery are dangerous. As a further safety measure this HRC type fuse should be located outside of the battery box, below the vent level of the batteries and before the positive and negative cables come close to each other.

Please note that 12/24V DC cables and fuses should be physically separate from 230V cables and fusing.

For medium size solar systems we sell a nice Distribution Board with large links to take up to 24mm sq cable. There is a circuit for solar (25A); 3 loads (10A) and an auxiliary (25A). The rating of these breakers can be altered if required and a further 3 breakers can be added to the box if required.

That's all for this month, folks. Please feel free to email me any comments or questions or anything you'd like to see in our newsletter.
Maybe you'd like to write an article about your own experiences!

Cheers from Dave and all the RPC crew.

Dave Lambert (Director)

+-2011 Newsletters

+-2010 Newsletters

+-2009 Newsletters

+-2008 Newsletters

+-2007 Newsletters

+-2006 Newsletters

+-2005 Newsletters

+-2004 Newsletters

+-2003 Newsletters

+-2002 Newsletters

+-2001 Newsletters

+-2000 Newsletters

+-1999 Newsletters

+-1998 Newsletters

+-1997 Newsletters



We install solar systems in Northern NSW and Southern QLD.


QLD:
Gold Coast (from Coolangatta to Southport), Nerang and Hinterland (Beaudesert) and out West (Warwick, Stanthorpe, Killarney)


NSW:
Northern NSW (Tweed Heads to Yamba, including Evans Head, Byron Bay and Ballina); the Far North Coast Hinterland (Grafton via Lismore to Murwillumbah) and out West (Casino to Tenterfield, including Drake and Tabulam, as well as Woodenbong and Bonalbo)

For larger system we also go up to Brisbane or down to Coffs Harbour and even Glen Innes. Other places by arrangement.